Guangzhou Hiseer Air Conditioning Co.,Ltd
|
|
| |
| Products |
|
 |
Ground Source Heat Pump Water Heater with Cooling R410A |
|
|
|

|

|
Click to enlarge image
|
Origin |
China |
Model Number |
GHP09B/10B/12B/13B/15B |
Heating, cooling and domestic hot water; Single phase with built-in soft-starter Adopt Siemens controller Daikin/Hitachi Scroll compressor Swep plate heat exchanger Varied heat curve Optional part: Internal 3KW electric heater Rust free Galvanized sheet cabinet Quiet running design for indoor installation
| Heat pump |
Type
|
GHP09B
|
GHP12B
|
GHP10B
|
GHP13B
|
GHP15B
|
| Dimensions,weights,connection dimensions |
| Dimensions |
HxWxD
|
960x600X600
|
| Weight |
kg
|
135
|
145
|
135
|
145
|
155
|
|
Refrigerant
|
Type
|
R410A
|
| Filling weight |
kg
|
1.7
|
1.8
|
1.7
|
1.8
|
2
|
| Permissible operating pressure |
Mpa
|
4.2
|
4.2
|
4.2
|
4.2
|
4.2
|
| Pipe connector-hot side |
Inch
|
G1”
|
G11/4”
|
G1”
|
G11/4”
|
G11/4”
|
| Pipe connector-cold side |
Inch
|
G1”
|
G11/4”
|
G1”
|
G11/4”
|
G11/4”
|
| Evaporator |
Type
|
Brazed plate heat exchanger
|
| Condenser |
Type
|
Brazed plate heat exchanger
|
| Compressor |
ã |
1xScroll
|
| Performance Heat pump |
| Heat output |
at B0/W35 |
kW
|
8.60
|
11.80
|
10
|
13
|
15.5
|
| Power consumption |
kW
|
1.95
|
2.70
|
2.22
|
2.9
|
3.5
|
| Performance factor |
ã |
4.41
|
4.37
|
4.5
|
4.48
|
4.43
|
| Hot side volume flow |
m3/h
|
1.48
|
2.03
|
1.72
|
2.24
|
2.67
|
| Cold side volume flow |
m3/h
|
1.91
|
2.61
|
2.23
|
2.90
|
3.44
|
| Heat output |
at W10/W35 |
kW
|
11.00
|
15.00
|
12.7
|
16.3
|
19.5
|
| Power consumption |
kW
|
2.03
|
2.80
|
2.27
|
2.96
|
3.57
|
| Performance factor |
ã |
5.42
|
5.36
|
5.59
|
5.51
|
5.46
|
| Hot side volume flow |
m3/h
|
1.89
|
2.58
|
2.18
|
2.80
|
3.35
|
| Cold side volume flow |
m3/h
|
2.57
|
3.50
|
2.99
|
3.82
|
4.57
|
| Cool output |
at W35/W7
|
kW
|
9.30
|
12.70
|
10.60
|
13.90
|
16.30
|
|
Power consumption
|
kW
|
2.00
|
2.70
|
2.20
|
2.85
|
3.40
|
|
Performance factor
|
ãÂÂ
|
4.65
|
4.70
|
4.82
|
4.88
|
4.79
|
|
Inside volume flow
|
m3/h
|
1.60
|
2.18
|
1.82
|
2.39
|
2.80
|
|
Outside volume flow
|
m3/h
|
1.94
|
2.65
|
2.20
|
2.88
|
3.39
|
|
Power
|
Type
|
Single phase with Darkin compressor
|
Triple phase with Hitachi compressor
|
|
Sound power level
|
dB(A)
|
47
|
48
|
47
|
48
|
48
|
| The above data is tested by EN14511 |
|
|
|
|
|
|
|
Delivery lead time |
20-25 days |
Minimum order |
1 unit |
|
|
| |
|
|
|